Skip to main content
3RT23162BB40

3RT23162BB40 Contactors (Electromechanical) | siemens

MPN3RT23162BB40Compare · similar
Active · In production

3RT23162BB40 (siemens) Contactors (Electromechanical). Series 3RT2; Package Bulk; Features Auxiliary Contacts. RFQ for MOQ and lead time.

PackagingBulk
Volume pricing1+ $102.04000
StockOut of Stock

Specifications

3RT23162BB40 Technical Specifications - Column 1
ParameterValue
RoHSROHS3 Compliant
StatusActive
FeaturesAuxiliary Contacts
Coil Power4 W
Coil Voltage24VDC
Coil Resistance144Ohms
Termination StyleSpring Terminal
Must Operate Voltage19.2 VDC
Contact Rating (Current)18 A
3RT23162BB40 Technical Specifications - Column 2
ParameterValue
Series3RT2
PackageBulk
MountingChassis Mount, DIN Rail
Coil Current166.7 mA
Contact Form4PST-NO (4 Form A)
Switching Voltage690VAC - Max
Base Product Number3RT2316
Operating temperature25°C to 60°C

Product details

Siemens 3RT23162BB40 Contactor

3RT2316 Series — S00 Frame, 18 A, DC Coil

The 3RT2316 base number identifies the Siemens SIRIUS S00 line of electromechanical contactors. The "BB40" suffix designates a 24 VDC coil with four normally-open main poles. The suffix structure across this series encodes coil voltage and construction variant; the "BB" block consistently maps to DC operation while trailing digits indicate control voltage tier.

Coil draw at pickup reaches 166.7 mA, yielding 4 W holding power against 144 Ω measured resistance. Pickup threshold sits at 19.2 VDC — 80% of nominal coil voltage, matching common DC relay design margins.


Contact Arrangement and Ratings

SpecValue
Contact Form4PST-NO (4 Form A)
Contact Rating18 A
MountingChassis Mount, DIN Rail
EncapsulationBulk

Four independent Form A contacts serve as main power poles. "Auxiliary Contacts" noted in features indicates integral auxiliary blocks for control-circuit feedback — typical for motor-starter and power-distribution use. The bulk packaging reflects production-quantity orientation rather than retail blister packaging.


Coil Electrical Summary

ParameterValue
Coil Voltage24 VDC
Coil Power4 W
Coil Current166.7 mA
Coil Resistance144 Ω
Must Operate Voltage19.2 VDC

DC coils on Siemens S00 contactors exhibit higher inrush than equivalent AC units; the 4 W figure reflects holding-state consumption after initial energization. Panel designers should account for supply capacity during coil energization transients.


Compare — DC Coil Variants in 3RT2316 Series

The reader must qualify the following alternates independently for specific application requirements.

Spec3RT23162BB40 (seed)3RT23162BF403RT23162BM40
Coil Voltage24 VDC110 VDC220 VDC
Must Operate19.2 VDC88 VDC176 VDC
Contact Rating18 A18 A18 A
MountingChassis, DIN RailChassis, DIN RailChassis, DIN Rail
EncapsulationBulkBoxBox
Similarity1.01.0
  • 3RT23162BF40: 110 VDC coil — same contact rating and mounting. The higher control voltage reduces coil current to approximately 36 mA at holding; suited for DC distribution systems where 24 V is unavailable.
  • 3RT23162BM40: 220 VDC coil — identical contact and mounting specs. Matches common 220 VDC bus architectures found in telecom infrastructure and some industrial DC networks.
  • 3RT23161BB40: Shares all electrical parameters with the seed; the trailing "1" in the 8th character reflects a minor construction revision within the same family — verify interchangeability with the target equipment's dimensional and connector requirements.

Frequently asked questions

MOQ rules for 3RT23162BB40 (3RT23162BB40)?

Typical floor: Evaluation quantities are usually workable—confirm on RFQ.. Packaging and factory MOQs can differ; we reconcile on quote.

Are there catalog alternates or second-source candidates for 3RT23162BB40?

We screen on package, interface, headline electricals, and lifecycle cues visible here—not on marketing series names alone, and not as manufacturer interchange approval. Send target rails, loads, and clearance rules for a quote-backed short list.

What does this page list for “Switching Voltage” on 3RT23162BB40?

The storefront table shows **Switching Voltage**: 690VAC - Max. Treat it as a catalog snapshot—re-verify safety-critical ratings on the current manufacturer datasheet.

Catalog value for “Coil Power” (3RT23162BB40)?

**Coil Power** is recorded as **4 W** for 3RT23162BB40. If your drawing disagrees, the datasheet wins.

Typical use cases for 3RT23162BB40?

Application wording stays generic until your constraints are known; the part’s real job is defined by the parameters above.

Compare

Parametric matrix links; verify on the datasheet before BOM swaps.

N-way (8 parts) · columns 2+ sorted by Hub similarity to 3RT23162BB40

Technical resources

Lifecycle: ActiveRoHS: ROHS3 Compliant