Siemens 3RT20361KB40: 70A S2 Contactor for 24VDC Motor Control
The 3RT20361KB40 delivers a verified 70A contact rating across three power poles at up to 690VAC, driven by a 24VDC coil drawing 895.8 mA (coil resistance 26.8 Ohms). Must-operate voltage is 19.2 VDC; operate and release times are 80 ms and 55 ms respectively. Operating temperature range spans 25°C to 60°C. ROHS3 Compliant and REACH Unaffected status is documented; ECCN is EAR99 under HTSUS 8536.41.0045.
Pin-compatible base product number 3RT2036 anchors this MPN within the SIRIUS 3RT2 family. Panel builders substituting 3RT1-generation contactors can verify mechanical footprint and DIN-rail clip geometry against the datasheet before ordering.
Auxiliary contact configuration: one normally-open (1NO) contact feeds status signals to a PLC input, overload relay, or safety controller. Engineers specifying additional safety feedback paths should cross-reference the 1NO+1NC variant 3RT20361KB401AA0 or the 2NO+2NC variant 3RT20361KB44 within the same base number series.
Quick read: on-page parameter snapshot
- Coil Voltage: 24VDC
- Coil Current: 895.8 mA
Key Selection Data
- Coil: 24VDC, 21.5W, 895.8 mA, 26.8 Ohms
- Must-operate voltage: 19.2 VDC
- Contact rating: 70 A per pole (3PST-NO)
- Switching voltage: 690VAC maximum
- Operate / release time: 80 ms / 55 ms
- Operating temperature: 25°C to 60°C
- Mounting: Chassis or DIN Rail, screw terminal
- Package: Bulk (MOQ 1)
Procurement Notes
Alternative MPNs in This Series
Engineer's notes — electrical baseline
For siemens 3RT20361KB40 (CONTACTOR S2 50A 24VDC SCREW 1NO); category path: Relays > Contactors (Electromechanical); confirmed specs: series: 3RT2; Mounting Type: Chassis Mount, DIN Rail; Package: Bulk; Product Status: Active, anchor electrical decisions to the normalized key-values above—especially supply class, I/O style, and thermal/enclosure assumptions—before you freeze a BOM line.
Field notes for cabinet wiring checks
Commissioning should re-verify mechanical fit, torque specs, connector families, and field cable dress against the drawings; raw specs do not replace an on-site walk-through.
Selection notes — BOM and electrical class
Any part change starts with identical electrical interfaces and mechanical envelope on paper; treat any change in counts, ranges, or package style as a formal re-validation — never a casual swap.