Skip to main content
5SJ4206-7HG42

5SJ4206-7HG42 Circuit Breakers | siemens

MPN5SJ4206-7HG42Compare · similar
Active · In production

5SJ4206-7HG42 (siemens) Circuit Breakers. Series 5SJ4; Package Bulk; RoHS RoHS non-compliant. RFQ for MOQ and lead time.

PackagingBulk
Volume pricing1+ $136.71000
StockOut of Stock

Specifications

5SJ4206-7HG42 Technical Specifications - Column 1
ParameterValue
RoHSRoHS non-compliant
StatusActive
MountingDIN Rail
Approval AgencyCCC, CE, CSA, EAC, UL, VDE
Voltage Rating - AC400 V
Current Rating (Amps)6 A
5SJ4206-7HG42 Technical Specifications - Column 2
ParameterValue
Series5SJ4
PackageBulk
Actuator TypeLever
Number of Poles2
Voltage Rating - DC125 V

Product details

Siemens 5SJ4 Miniature Circuit Breaker

Key Specifications 5SJ4206-7HG42

SpecValue
Current Rating6 A
Voltage480/277 V AC
Number of Poles2
Trip CurveC (5–10× In)
Interrupt Rating10 kA
MountingDIN Rail
ActuatorLever
PackageBulk
  • IEC/EN 60898 Type C thermal-magnetic trip.
  • Multi-standard agency approvals: CCC, CE, CSA, EAC, UL, VDE.
  • RoHS non-compliant; sold as bulk packaging only.

5SJ4 Series — Two-Pole C-Trip Comparison

The reader must independently qualify all alternatives against their application before selection.

MPNCurrentVoltageTripInterruptPackageSimilarity
5SJ4206-7HG426 A480/277 VC10 kABulk
5SJ4206-7HG416 A240 VC14 kABulk1.0
5SJ42068HG426 A480/277 VD10 kABulk1.0
5SJ4206-8HG416 A240 VD14 kABox1.0
5SJ4203-7HG423 A480/277 VC10 kABulk1.0
5SJ4204-7HG424 A480/277 VC10 kABulk1.0
5SJ4201-7HG421 A480/277 VC10 kABulk1.0
5SJ4205-7HG42500 mA480/277 VC10 kABox1.0
5SJ4208-7HG428 A480/277 VC10 kABox1.0

Why similar: All share the Siemens 5SJ4 frame, two-pole DIN-rail form factor, and bulk or box packaging. The -7 suffix designates C-trip; the -8 variants switch to D-curve (10–20× In) with higher 240 V interrupt ratings.

Engineering Notes

  • The C-curve rating (5–10× nominal current) suits resistive and moderate inductive loads such as lighting branches and small motor feeders without excessive nuisance tripping on inrush.
  • The 10 kA interrupt rating at 480/277 V is adequate for branch protection in most commercial and light-industrial panels; verify fault current available at the point of installation does not exceed this.
  • All listed units are RoHS non-compliant; assess suitability for equipment destined for markets with substance restrictions.

Frequently asked questions

MOQ rules for 5SJ4206-7HG42 (5SJ4206-7HG42)?

Typical floor: Evaluation quantities are usually workable—confirm on RFQ.. Packaging and factory MOQs can differ; we reconcile on quote.

Are there catalog alternates or second-source candidates for 5SJ4206-7HG42?

We screen on package, interface, headline electricals, and lifecycle cues visible here—not on marketing series names alone, and not as manufacturer interchange approval. Send target rails, loads, and clearance rules for a quote-backed short list.

Typical use cases for 5SJ4206-7HG42?

Application wording stays generic until your constraints are known; the part’s real job is defined by the parameters above.

What does this page list for “Voltage Rating - DC” on 5SJ4206-7HG42?

The storefront table shows **Voltage Rating - DC**: 125 V. Treat it as a catalog snapshot—re-verify safety-critical ratings on the current manufacturer datasheet.

Catalog value for “Voltage Rating - AC” (5SJ4206-7HG42)?

**Voltage Rating - AC** is recorded as **400 V** for 5SJ4206-7HG42. If your drawing disagrees, the datasheet wins.

Compare

Parametric matrix links; verify on the datasheet before BOM swaps.

N-way (8 parts) · columns 2+ sorted by Hub similarity to 5SJ4206-7HG42

Technical resources

Lifecycle: ActiveRoHS: RoHS non-compliant