Skip to main content
14DUB320C

14DUB320C Motor Driver Boards, Modules | siemens

MPN14DUB320CCompare · similar
Active · In production

14DUB320C (siemens) Motor Driver Boards, Modules. Type Module; Package Box; RoHS RoHS non-compliant. RFQ for MOQ and lead time.

PackagingBox
Volume pricing1+ $707.71000
StockOut of Stock

Specifications

14DUB320C Technical Specifications - Column 1
ParameterValue
RoHSRoHS non-compliant
StatusActive
MountingChassis Mount
Motor TypeAC Motor
Output current27 A
Number of Motors1
Operating temperature20°C to 40°C
14DUB320C Technical Specifications - Column 2
ParameterValue
TypeModule
PackageBox
Load power1490 W
Load voltage600 V
Supply voltage220 to 480VAC
Control / Drive TypeMotor Starter

Product details

Siemens 14DUB320C FVNR Motor Starter

Specification Comparison — 14DUB320C vs. 14DUB320 Family

Specification14DUB320C (Seed)14DUB320D14DUB320J14DUB320ESimilarity (0–1)
Control / Drive TypeMotor StarterMotor StarterMotor StarterMotor Starter1.0
Current — Output27A27A27A27A1.0
Motor TypeAC MotorAC MotorAC MotorAC Motor1.0
Mounting TypeChassis MountChassis MountChassis MountChassis Mount1.0
Number of Motors11111.0
Operating Temperature20°C ~ 40°C20°C~40°C20°C~40°C20°C ~ 40°C1.0
EncapsulationBoxBoxBoxBulk
RoHSNon-compliantNot specifiedNon-compliantNot specified
Product StatusActiveActiveActiveActive1.0

The reader must qualify each alternate independently against application requirements. The shared axis across the family is a 27A-output FVNR (full-voltage non-reversing) Size 1 starter for AC motors, chassis-mounted, operating over 20°C–40°C.

Why these are similar:

  • 14DUB320D, 14DUB320J — same Box encapsulation and full spec overlap; distinguish only by RoHS notation or stock entry absence.
  • 14DUB320E — identical electrical and mechanical ratings; differs in Bulk packaging instead of Box, which affects unit quantity and may alter shelf-life handling.

Siemens 14DUB320C Core Parameters

ParameterValue
Control / Drive TypeMotor Starter (FVNR)
Current — Output27A
Motor TypeAC Motor
SizeSZ1
Current Adjustment Range0.75–3.4A
Number of Motors1
Mounting TypeChassis Mount
Operating Temperature20°C ~ 40°C
EncapsulationBox
RoHSNon-compliant
Product StatusActive

The SZ1 designation places this in Siemens' Size 1 envelope, governing physical dimensions and short-circuit coordination ratings typical for branch-circuit motor protection. The 0.75–3.4A adjustable range is the overload relay setting window; the 27A output rating is the contactor current capacity. FVNR topology applies full line voltage to the motor on start; it does not provide reversing or reduced-voltage starting.


Enclosure and Environmental Notes

The 20°C–40°C operating range is narrow and indicates an indoor, climate-controlled environment. No IP rating or enclosure type appears in the record; panel designers should verify that chassis mounting into a suitable enclosure provides adequate environmental protection for the target installation. The non-compliant RoHS status reflects legacy materials in the contactor and overload housing; replacement in new equipment subject to RoHS directives requires an alternative line or a confirmed RoHS-compliant variant.


Family Suffix Differentiation

MPNEncapsulationRoHSDistinguishing Note
14DUB320ABoxNon-compliantStandard baseline variant
14DUB320CBoxNon-compliantSeed unit
14DUB320DBoxNot specifiedIdentical to seed; stock entry differs
14DUB320EBulkNot specifiedBulk packaging; may affect MOQ
14DUB320FBoxNon-compliantStandard variant
14DUB320GBoxNot specifiedIdentical to seed; stock entry differs
14DUB320HBoxNon-compliantStandard variant
14DUB320JBoxNon-compliantStandard variant
14DUB32ACBoxNon-compliantDiffers in title descriptor only; specs align

The 14DUB32AC entry carries the title "OPEN STARTER 240/480V" but shares all recorded electrical and mechanical specifications with the 14DUB320x series. Title variation alone does not imply a different voltage rating without confirmed datasheet documentation.


Frequently asked questions

Who can validate 14DUB320C against my schematic?

Start from this page’s spec snapshot, attach your critical nets, and request a structured comparison on RFQ.

Is 14DUB320C appropriate for my panel design?

We start from the values printed in the specification table, then ask for one-line diagrams or net names that matter for your branch.

What can substitute for 14DUB320C if supply tightens?

We narrow candidates from footprint, voltage/current class, and approvals visible on this page. Any change still needs your datasheet review and hardware qualification—not a guaranteed substitute from storefront text.

What is the minimum order quantity (MOQ) for 14DUB320C?

MOQ for 14DUB320C: Evaluation quantities are usually workable—confirm on RFQ.. Pilot builds can often start smaller—state your target annual usage in the RFQ.

Catalog value for “Number of Motors” (14DUB320C)?

**Number of Motors** is recorded as **1** for 14DUB320C. If your drawing disagrees, the datasheet wins.

Compare

Parametric matrix links; verify on the datasheet before BOM swaps.

N-way (2 parts) · columns 2+ sorted by Hub similarity to 14DUB320C

No extra ranked peers — use featured pair or hub.

Technical resources

Lifecycle: ActiveRoHS: RoHS non-compliant