In a main-breaker or subdistribution panel, the 3VA5220-5ED61-0AA0 occupies a DIN-rail position in the 3VA52 family (Siemens SENTRON series), providing branch protection for motors or feeder circuits where thermal-magnetic tripping characteristics are specified. The catalog record lists 200 A at up to 35 kA interrup...

Siemens 3VA5220-5ED61-0AA0 Molded Case Circuit Breaker

3VA52 Series: 200 A, 35 kA, 2P/3P Configurable, FTFM Type

In a main-breaker or subdistribution panel, the 3VA5220-5ED61-0AA0 occupies a DIN-rail position in the 3VA52 family (Siemens SENTRON series), providing branch protection for motors or feeder circuits where thermal-magnetic tripping characteristics are specified. The catalog record lists 200 A at up to 35 kA interrupt, lever actuation, and multi-agency certifications covering CCC, CE, CSA, EAC, UL489, and VDE.

Key Specifications

ParameterValue
Series3VA52 (SENTRON)
Current Rating200 A
Interrupt Rating35 kA
Number of Poles2 (2(3)P selectable)
Actuator TypeLever
MountingDIN Rail
IlluminationNone
Encapsulation / PackageBox
Product StatusActive
RoHSNon-compliant

Certifications on record: CCC, CE, CSA, EAC, UL489, VDE.

Selection Trade-offs from On-Record Specs

  1. 2P vs. 3P pole count: Title indicates "2(3)P" — the unit is configurable for two-pole protection with an optional third pole. Verify coordination requirements for grounded-neutral or three-phase schemes before specifying the mechanical pole arrangement on the rail.
  2. FTFM trip type: "FTFM" denotes Frame/Thermal/Fixed/Magnetic — the fixed magnetic adjustment window constrains coordination flexibility versus adjustable-trip variants; confirm that the specified magnetic setting aligns with the prospective short-circuit current of the protected bus.
  3. 35 kA at rated voltage: The interrupting rating is stated as 35 kA; do not exceed the voltage rating associated with the fault rating in the target installation without verifying that the applied voltage stays within the breaker's dielectric limits.
  4. RoHS non-compliant: This part carries no RoHS compliance notation. For installations in regions or sectors with environmental material restrictions, confirm suitability before release to procurement.
  5. No integral illumination: The actuator lacks integrated status illumination; for remote indication or door-interlock feedback, external auxiliary contact modules or motor operators (if listed in the SENTRON accessories family) may be required separately.

Integration Notes

  • Mounting is DIN rail per the catalog record; ensure adequate rail type and enclosure depth clearance for lever throw.
  • Actuator is a manual lever — no motor operator or electrical remote-trip mechanism is listed in the available specs.
  • No illumination on the actuator; status signaling requires external auxiliary contacts if needed.

Similar Catalog Parts

The following parts share the 3VA52 series foundation with the primary part. They require the reader's own qualification before use as alternatives.

Parameter3VA5220-5ED61-0AA03VA52205ED310AA03VA5220-5EC61-0AA0
Poles2(3)P3P2(3)P
Current Rating200 A200 A200 A
Interrupt Rating35 kA35 kA35 kA
MountingDIN RailDIN RailDIN Rail
Actuator TypeLeverLeverLever
IlluminationNoneNoneNone
CertificationsCCC, CE, CSA, EAC, UL489, VDECCC, CE, CSA, EAC, UL489, VDE
Similarity1.00.96

3VA52205ED310AA0: Same series, 3-pole fixed version of the 200 A / 35 kA unit. The reason string cites shared series, illumination, actuator type, mounting type, encapsulation, voltage rating, and current rating. Pole count is the primary structural difference; the three-pole variant suits three-phase protection schemes where the primary part's selectable-pole configurability is not required.

3VA5220-5EC61-0AA0: Matches the primary part's two-pole selectable configuration, 200 A, lever actuator, and same certifications (CCC, CE, CSA, EAC, UL489, VDE). The reason string cites a different internal designation ("FTAM" rather than "FTFM") indicating a variant within the same frame family — the reader should confirm trip characteristic alignment before substituting.

FAQ

What is the trip type of the 3VA5220-5ED61-0AA0? The catalog title specifies "FTFM," denoting Fixed thermal-magnetic tripping with a fixed magnetic element. Detailed curve values are not listed in the available record.

Can the 3VA5220-5ED61-0AA0 be used for three-phase protection? The title indicates "2(3)P," meaning the unit can be configured with an optional third pole for three-phase schemes. Verify whether the specific order-code configuration includes the third pole kit or requires separate ordering.

Is the 3VA5220-5ED61-0AA0 RoHS compliant? No — the RoHS status field lists "RoHS non-compliant."