Siemens 3RT20151AB01 Contactors

The Siemens 3RT2015 series positions 7 A electromechanical contactors for light motor and distribution duties in control panels. Variant selection hinges on four parameters recorded across catalog entries:

Siemens 3RT20151AB01 Contactors

Selection trade-offs for the 3RT2015 family

The Siemens 3RT2015 series positions 7 A electromechanical contactors for light motor and distribution duties in control panels. Variant selection hinges on four parameters recorded across catalog entries:

  1. Coil voltage selection: Catalog entries span 24 VAC through 400 VAC. Must-operate voltage scales proportionally (20.4 VAC at 24 VAC coil; 340 VAC at 400 VAC coil). Mismatched coil voltage prevents pickup regardless of load-side ratings.
  2. Auxiliary contact arrangement: The 3RT20151AB01 carries one normally-open (1NO) auxiliary contact. Alternates 3RT20151AB02 and 3RT20151AB021AA0 specify normally-closed (1NC) auxiliary in otherwise identical packages. Control-circuit logic type (hold-in vs dropout) governs which arrangement suits a given schematic.
  3. Encapsulation and packaging: The seed variant lists Bulk packaging; several alternates (3RT20151AB011AA0, 3RT20151AB012AA0, 3RT20151AV01, 3RT20151AD01, 3RT20151AQ01, 3RT20151AH01) are cataloged as Box. Unit quantity and handling preferences may dictate which package form suits a given order.
  4. Coil power consumption: Alternates with Box encapsulation specify 24.3 VA pull; the 3RT20151AB02 (Bulk) lists 27 VA. Power-supply sizing and thermal headroom in enclosed panels follow from these figures.

Key specifications (3RT20151AB01)

ParameterValue
Base Product Number3RT2015
Contact Form3PST-NO (3 Form A)
Contact Rating7 A
Coil Voltage24 VAC
Must Operate Voltage20.4 VAC
Operate Time35 ms
Mounting TypeChassis Mount, DIN Rail
Operating Temperature25°C ~ 60°C
FeaturesAuxiliary Contacts
EncapsulationBulk

Catalog comparison — 3RT2015 variants

MPNCoil VoltageContact FormMust OperateCoil PowerEncapsulationSimilarity
3RT20151AB0124 VAC3PST-NO (1NO aux)20.4 VACBulk1.0
3RT20151AB011AA024 VAC3PST-NO (1NO aux)20.4 VAC24.3 VABox1.0
3RT20151AB012AA024 VAC3PST-NO (1NO aux)20.4 VAC24.3 VABox1.0
3RT20151AB0224 VAC3PST-NO (1NC aux)20.4 VAC27 VABulk1.0
3RT20151AV01400 VAC3PST-NO (1NO aux)340 VAC24.3 VABox0.96
3RT20151AD0142 VAC3PST-NO (1NO aux)35.7 VAC24.3 VABox0.96

The top three similarity-1.0 alternates differ from the seed only in packaging and (for the 3RT20151AB02) auxiliary contact state. These variants require the reader's own engineering qualification before substitution.

Why these variants appear similar: All share the 3RT2015 base product number, 7 A contact rating, three-pole normally-open arrangement, 35 ms operate time, and DIN Rail / chassis mounting. The must-operate voltage threshold and coil power diverge only as a direct function of the coil voltage chosen across the family range.

FAQ

Does the 3RT20151AB01 include an auxiliary contact? Yes — the catalog entry lists "Auxiliary Contacts" under Features; the contact form is specified as 3PST-NO with one normally-open auxiliary contact.

What coil voltage does the 3RT20151AB01 require? The specified coil voltage is 24 VAC with a must-operate threshold of 20.4 VAC.

Can a 400 VAC coil variant replace the 24 VAC version in the same enclosure footprint? No — coil voltage is a fixed selection per unit; swapping to 3RT20151AV01 or other higher-voltage coils requires a different control transformer or supply arrangement and re-verification of must-operate voltage against the available control voltage.